SPECIFICATIONS
GENERATOR
Type......................................................................Synchronous
Total Harmonic Distortion ..............................................< 3.5%
Telephone Interference Factor (TIF) .................................. < 50
Alternator Output Leads 1-phase ..................................... 4-wire
Alternator Output Leads 3-phase (150kW)....................... 6-wire
Alternator Output Leads 3-phase (100/130kW) ............. 12-wire
Bearings ..................................................................Sealed Ball
Coupling
100/130kW ............................................................Gear Drive
150kW.................................................................Flexible Disk
Excitation System ......................................................Brushless
Circuit Breaker Size (Amps)
Voltage 100kW 130kW 150kW
120/240V - 1ø 500 600 700
120/208V - 3ø 400 500 600
120/240V - 3ø 350 450 500
277/480V - 3ø 175 225 250
600V - 3ø 150 N/A 200
Generator Locked Rotor KVA Available @ Voltage Dip of 35%
100kW 130kW 150kW
240V, 1-phase
240V, 3-phase
208V, 3-phase
206 270 313
480V, 3-phase 275 320 350
600V, 3-phase 275 N/A 350
Refer to the Data Label on the generator for rated watts, amperes, frequency, volt-
age, phase and other pertinent information.
NOTE: Generator rating and performance in accordance with ISO8528-5, BS5514,
SAE J1349, ISO3046 and DIN 6271 Standards. KW rating is based on LPG fuel
and may derate with natural gas.
ENGINE
Make ........................................................................... Generac
Model ............................................................................. V-type
Cylinders and Arrangement ...................................................10
Displacement ............................................................... 6.8 Liter
Bore..............................................................................3.55 in.
Stroke ...........................................................................4.17 in.
Compression Ratio.......................................................... 9-to-1
Air Intake System ......................................... Naturally Aspirated
Valve Seats ................................................................ Hardened
Lifter Type .................................................................. Hydraulic
Engine Parameters
Rated Synchronous RPM ...................................See Data Label
Gross HP at rated kW
NG (100/130/150) ................................60 Hz, (149/192/231)
LP (100/130/150).................................60 Hz, (162/208/231)
Exhaust System
Exhaust Flow at Rated Output 60 Hz ........................See Chart 1
Exhaust Temperature at Rated Output ......................See Chart 1
Combustion Air Requirements (Natural Gas)
Flow at rated power, 60 Hz ......................................See Chart 1
Chart 1
kW
Exhaust Flow
CFM
Exhaust Temp °F
Combustion Air
Flow CFM
100 888 960 262
130 1119 970 336
150 1535 1100 410
Governor
Type...........................................................................Electronic
Frequency Regulation .............................................Isochronous
Steady State Regulation ..............................................± 0.25%
Adjustments:
Speed ............................................................................... Yes
Droop ............................................................................... Yes
Engine Lubrication System
Type of Oil Pump ...............................................................Gear
Oil Filter .......................................................Full Flow, Cartridge
Crankcase Oil Capacity ............................................ 5 U.S. qts.
COOLING SYSTEM
Type............................................................................... Closed
Water Pump ............................................................. Belt Driven
Fan Speed ...............................................................See Chart 2
Fan Diameter ..............................................................26 inches
Fan Mode ......................................................................... Puller
Air Flow (inlet air including alternator and
combustion air) ....................................................See Chart 2
Coolant Capacity ................................................. (4.5 U.S. gal.)
Heat Rejection to Coolant ........................................See Chart 2
Maximum Operating Air Temp. on Radiator ......... 60° C (150° F)
Maximum Ambient Temperature ......................... 50° C (140° F)
Maximum External Press. Drop on Radiator ................. 0.5" H
2
0
Chart 2
kW
Cooling Airflow
ft
3
/min
Fan Speed RPM
Heat Rejection
BTU/hr
100 5500 1670 342,000
130 6450 1950 496,000
150 7800 2200 568,000
6-1
Stationary Emergency Generator
Specifications
GenSpec073 Rev. A 06/09