Handleiding voor je System Sensor CO1224TR Koolmonoxidemelder nodig? Hieronder kun je de handleiding gratis bekijken en downloaden als PDF in het Nederlands en/of Engels. Dit product heeft 0 veelgestelde vragen, 0 comments en heeft 0 stemmen. Is dit niet de handleiding die je zoekt, neem dan contact met ons op.

Is je product kapot en biedt de handleiding geen oplossing meer? Dan kun je voor reparatie gratis terecht bij Repair Café.

Handleiding

Loading…

CO1224T/CO1224TR
Carbon Monoxide Detector
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6583
www.systemsensor.com
SPECIFICATIONS
Electrical Specifications
System Voltage Nominal: 12/24 VDC
Min: 10 VDC
Max: 33 VDC
Avg. Standby Current: 20 mA
Max Alarm Current: 40 mA (75 mA test)
Alarm Contact Ratings: 30 VDC @ 0.5 A
Trouble Contact Ratings: 30 VDC @ 0.5 A
Audible Signal (temp 4 tone): 85 dBA min. in alarm (at 10ft)
Max. Start-up Capacitance: 20 uF
Physical Specifications
Operating Temperature Range: 0° to 40°C (32° to 104°F)
Operating Humidity Range: 22 – 90% %RH
Diameter: 6.0˝
Height: 1.25˝
Weight: 7 oz
Wire Gauge Acceptance: 14-22 AWG
NOTICE: This manual shall be left with the owner/user of this equipment.
This product is intended for use in ordinary indoor locations.
GENERAL DESCRIPTION
Listed to standard 2075
Round shape allows for mounting in aesthetically demanding areas
Six-wire, system monitored
Optional CO detector replacement plate for previously installed detectors
Local sounder
Low current draw
Alarm relay, Form C
Trouble relay, Form A
Dual LED’s
Test/Hush button
SEMS wiring terminals
Mount to single gang electrical box or surface mount to wall or ceiling
Optional drywall anchors included
TABLE 1. DETECTOR OPERATION MODES:
OPERATION
MODE
GREEN LED RED LED SOUNDER
Normal
(standby)
Blink 1
per minute
OFF OFF
Alarm OFF Temp 4*pattern Temp 4* pattern
Alarm Test OFF Temp 4 pattern Temp 4 pattern
RealTest®
Mode
Blink 1
per second
OFF
Temp 4 pattern
(after CO is sprayed)
End of Life OFF OFF OFF
CO Trouble OFF
Blink 1
per minute
OFF
Power Loss/
Cell Fault
OFF OFF OFF
Alarm Test: Will send alarm signal to panel.
Hush feature/Alarm Silence: If required, the audible alarm can be silenced
for 5 minutes by pushing the button marked “Test/Hush”. The red alarm light
will continue to flash in temp-4 pattern. If carbon monoxide is still present
after the 5 minute hush period, the audible alarm will sound. The hush facility
will not operate at levels above 350 ppm (parts per million) carbon monoxide.
RealTest® Alarm Silence: Alarm will automatically silence after about 20 sec
-
onds of alarm from spraying canned CO into the detector. Alarm Reset: Alarm
automatically resets after CO has cleared from the sensor.
Trouble feature: When the sensor supervision is in a trouble condition (e.g.
such as a sensor that has been tampered with, or the cell itself has prema-
turely dried out due to environmental conditions, etc.), the detector will send
a trouble signal to the panel. The detector must then be replaced. The green
LED turns off and the red LED blinks every minute when the detector is in
trouble.
End of Life Timer feature: When the detector has reached the end of its life,
the trouble contact will open. This indicates that the CO sensor inside the
detector has passed the end of its life and must be replaced. This detector’s
lifespan is approximately ten years from the date of manufacture. The green
LED turns off when the detector is in trouble. Periodically check the “Replace
by” sticker located under the detector cover. The detector must be replaced by
this date. Refer to Detector Replacement on page 3.
Per UL 2075, it is mandatory that a trouble signal be sent to the panel
upon CO cell trouble or cell end of life. Refer to Figure 4 for wiring of the
trouble relay.
I56-3111-012
LIVING
ROOM
BEDROOM BEDROOM
BEDROOM
KITCHEN
TO
BR
CLOSED
DOOR
BASEMENT
GARAGE
CARBON MONOXIDE/SMOKE ALARM
LOCATION FOR MULTI-LEVEL RESIDENCE
S0295-01
FIGURE 1. ALARM LOCATION DIAGRAM:
1 I56-3111-012
10-28
Download de handleiding in het Nederlands en/of Engels (PDF, 0.85 MB)
(Denk aan het milieu en print deze handleiding alleen als dat echt noodzakelijk is)

Loading…

Beoordeling

Laat ons weten wat je van de System Sensor CO1224TR Koolmonoxidemelder vindt door een beoordeling achter te laten. Wil je je ervaringen met dit product delen of een vraag stellen? Laat dan een bericht achter onderaan de pagina.
Bent u tevreden over de System Sensor CO1224TR Koolmonoxidemelder?
Ja Nee
Beoordeel dit product als eerste
0 stemmen

Praat mee over dit product

Laat hier weten wat jij vindt van de System Sensor CO1224TR Koolmonoxidemelder. Als je een vraag hebt, lees dan eerst zorgvuldig de handleiding door. Een handleiding aanvragen kan via ons contactformulier.

Meer over deze handleiding

We begrijpen dat het prettig is om een papieren handleiding te hebben voor je System Sensor CO1224TR Koolmonoxidemelder. Je kunt de handleiding bij ons altijd downloaden en daarna zelf printen. Indien je graag een originele handleiding wilt hebben, raden we je aan contact op te nemen met System Sensor. Zij kunnen wellicht nog voorzien in een originele handleiding. Zoek je de handleiding van System Sensor CO1224TR Koolmonoxidemelder in een andere taal? Kies op de homepage je taal naar keuze en zoek daarna op het modelnummer om te zien of we deze beschikbaar hebben.

Specificaties

Merk System Sensor
Model CO1224TR
Categorie Koolmonoxidemelders
Bestandstype PDF
Bestandsgrootte 0.85 MB

Alle handleidingen voor System Sensor Koolmonoxidemelders
Meer handleidingen voor Koolmonoxidemelders

Handleiding System Sensor CO1224TR Koolmonoxidemelder

Gerelateerde producten

Gerelateerde categorieën